Maximum continuous voltage UC (line-line)
≤ 3.3 V DC (±60 V DC/PoE+)
Product type
Surge protection for information technology
Operating effective current IC at UC
Protective conductor current IPE
Nominal discharge current In (8/20) µs (line-line)
Type
Attachment plug for DIN rail mounting
Nominal discharge current In (8/20) µs (line-ground)
Pulse discharge current Iimp (10/350) µs (line-earth)
Surge protection fault message
Total discharge current ITotal (8/20) µs
Residual voltage at In (conductor-conductor)
Voltage protection level Up (line-line)
≤ 100 V (B2 - 1 kV / 25 A - PoE)
≤ 12 V (C3 - 20 A)
≤ 9 V (B2 - 1 kV / 25 A)
Voltage protection level Up (line-earth)
≤ 1 kV (C3 - 80 A)
≤ 700 V (C2 - 4 kV / 2 kA)
≤ 900 V (B2 - 4 kV / 100 A)
Response time tA (line-line)
Response time tA (line-earth)
Direction of action
Line-Line & Line-Ground/Shield
Maximum continuous voltage U<sub>C</sub> (line-line)
≤ 3.3 V DC (±60 V DC/PoE+)
Operating effective current I<sub>C</sub> at U<sub>C</sub>
Protective conductor current I<sub>PE</sub>
Nominal discharge current I<sub>n</sub> (8/20) µs (line-line)
Nominal discharge current I<sub>n</sub> (8/20) µs (line-ground)
Pulse discharge current I<sub>imp</sub> (10/350) µs (line-earth)
Total discharge current I<sub>Total</sub> (8/20) µs
Nominal pulse current Ian (10/700) µs (line-line)
Nominal pulse current Ian (10/700) µs (line-earth)
Output voltage limitation at 1 kV/µs (line-line) spike
Output voltage limitation at 1 kV/µs (line-earth) spike
Output voltage limitation at 1 kV/µs (line-line) static
Output voltage limitation at 1 kV/µs (line-earth) static
Residual voltage at I<sub>n</sub> (conductor-conductor)
Voltage protection level U<sub>p</sub> (line-line)
≤ 100 V (B2 - 1 kV / 25 A - PoE)
≤ 12 V (C3 - 20 A)
≤ 9 V (B2 - 1 kV / 25 A)
Voltage protection level U<sub>p</sub> (line-earth)
≤ 1 kV (C3 - 80 A)
≤ 700 V (C2 - 4 kV / 2 kA)
≤ 900 V (B2 - 4 kV / 100 A)
Response time t<sub>A</sub> (line-line)
Response time t<sub>A</sub> (line-earth)
Input attenuation aE, sym.
≤ 1 dB (up to 100 MHz/direct measuring)
≤ 1 dB (up to 250 MHz/direct measuring)
≤ 3 dB (up to 500 MHz/direct measuring)
Near-end crosstalk attenuation
≥ 27 dB (500 MHz / 100 Ω / Link)
≥ 35 dB (250 MHz/100 Ω/link)
≥ 39 dB (250 MHz/100 Ω/direct measuring)
≥ 45 dB (100 MHz / 100 Ω / Link)