Input voltage range in reference to UN
Set comprises
2909739 RIF-2-RPT-LV-230AC/4X21/EX
Typical input current at UN
Mechanical service life
approx. 2x 10<sup>7</sup> cycles
Date of last data management
Maximum power dissipation for nominal condition
Test voltage (Winding/contact)
2.5 kV<sub>rms</sub> (50 Hz, 1 min., winding/contact)
Test voltage (Changeover contact/changeover contact)
2 kV<sub>rms</sub> (50 Hz, 1 min., changeover contact/changeover contact)
Nominal input voltage U<sub>N</sub>
Input voltage range
179.4 V AC ... 317.4 V AC
Input voltage range in reference to U<sub>N</sub>
Typical input current at U<sub>N</sub>
Typical response time
5 ms ... 15 ms (depending on phase relation)
Typical release time range
5 ms ... 20 ms (depending on phase relation)
Maximum switching voltage
Minimum switching voltage
Limiting continuous current
Maximum inrush current
16 A (20 ms, N/O contacts)
Interrupting rating (ohmic load) max.
108 W (at 60 V DC)
124 W (at 48 V DC)
144 W (at 24 V DC)
1500 VA (for 250 V AC)
48 W (at 220 V DC)
52 W (at 110 V DC)
Switching capacity
0.11 A (at 250 V, DC13)
0.22 A (at 120 V, DC13)
1 A (at 240 V, AC15)
1.5 A (at 120 V, AC15)
1.5 A (at 24 V, AC15)
2 A (at 24 V, DC13)
Motor load according to UL 508
Ambient temperature (operation)
Ambient temperature (storage/transport)
Identification
EN 60068-2-60
ISA-S71.04. G3 Harsh Group