Typ. starting time with Us
< 200 ms (with Us / when controlled via A1)
Rated control circuit supply voltage US
Application
Emergency stop
Safety door
Rated control supply current IS
typ. 100 mA (at U<sub>S</sub>)
Mechanical service life
10x 10<sup>6</sup> cycles
approx. 10<sup>7</sup> cycles
Relay type
Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Typical response time
< 120 ms (For U<sub>s </sub>autostart)
< 140 ms (For U<sub>s </sub>manual, monitored start)
Typ. starting time with U<sub>s</sub>
< 200 ms (with Us / when controlled via A1)
Typical release time
< 20 ms (At Us on demand via sensor circuit)
< 50 ms (At Us/on demand via A1)
Recovery time
250 ms (Availability time after activating the sensor circuit during manual start)
500 ms (following demand of the safety function)
Start pulse length
min. 500 ms (manual start)
Maximum power dissipation for nominal condition
31.7 W (U<sub>S</sub> = 26.4 V, I<sub>L</sub>² = 144 A², P<sub>Total max</sub> = 2.9 W + 28.8 W)
Rated surge voltage/insulation
See data sheet, section “Insulation coordination”.
Rated control circuit supply voltage U<sub>S</sub>
Rated control supply current I<sub>S</sub>
typ. 100 mA (at U<sub>S</sub>)
Power consumption at U<sub>S</sub>
Inrush current
< 10 mA
max. -180 mA (Δt = 1 ms, with U<sub>s</sub>/I<sub>x</sub> at S22)
max. 150 mA (Δt = 1 ms, with U<sub>s</sub>/I<sub>x</sub> at S10)
max. 200 mA (Δt = 1 ms, with U<sub>s</sub>/I<sub>x</sub> at S12)
max. 6 A
min. 10 mA
min. 10 mA AC/DC
typ. 3.5 A (with U<sub>S</sub>, Δt = 2 ms)
Filter time
2 ms (in the event of voltage dips at U<sub>s</sub>)
max. 1.5 ms (Test pulse width, low test pulses (S10, S12) )
No brightness test pulses / high test pulses permitted.
No test pulses permitted
Test pulse rate = 5 x test pulse width, low test pulses (S10, S12)
Protective circuit
Serial protection against polarity reversal; Suppressor diode
Suppressor diode
Description of the input
non-safety-related
safety-related
Input voltage range "0" signal
0 V DC ... 5 V DC (S10, S12)
S22 open
Input voltage range "1" signal
0 V ... 0 V (S22)
20.4 V ... 26.4 V
20.4 V ... 26.4 V (S10, S12)
Input current range "0" signal
Max. permissible overall conductor resistance
Current consumption
-50 mA (S22)
0 mA (S34)
1 mA (S35)
50 mA (S10, S12)
Output description
2 N/C contacts parallel, non-safety-related, floating
2 N/O contacts each in series, safety-related, floating
Contact switching type
1 signaling current path
8 enabling current paths
Switching voltage
max. 250 V AC/DC
min. 5 V AC/DC
Switching capacity
1.5 A (AC15)
3 A (AC15)
5 A (DC13)
Limiting continuous current
6 A
6 A (observe derating)
Sq. Total current
144 A<sup>2</sup> (observe derating)
36 A<sup>2</sup>
Output fuse
10 A gL/gG
4 A gL/gG (Low demand)
6 A gL/gG
6 A gL/gG (Low demand)