Rated control circuit supply voltage US
Rated control supply current IS
Application
Emergency stop
Light grid
Safety door
Typ. starting time with Us
< 600 ms (when controlled via A1)
Mechanical service life
10x 10<sup>6</sup> cycles
Relay type
Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Maximum power dissipation for nominal condition
Rated surge voltage/insulation
Rated control circuit supply voltage U<sub>S</sub>
20.4 V DC ... 26.4 V DC
24 V DC -15 % / +10 %
Power consumption at U<sub>S</sub>
Rated control supply current I<sub>S</sub>
Inrush current
< 150 mA (with U<sub>s</sub>/I<sub>x </sub>to S12)
< 40 mA (with U<sub>s</sub>/I<sub>x </sub>to S10)
> -60 mA (with U<sub>s</sub>/I<sub>x </sub>to S22)
200 mA (at U<sub>S</sub>)
Current consumption
< 40 mA (with U<sub>s</sub>/I<sub>x </sub>to S10)
> -40 mA (with U<sub>s</sub>/I<sub>x </sub>to S22)
0 mA (with U<sub>s</sub>/I<sub>x </sub>to S34)
Voltage at input/start and feedback circuit
Filter time
1 ms (at A1 in the event of voltage dips at U<sub>s</sub>)
7.5 ms (at S10, S12; test pulse rate)
max. 1.5 ms (at S10, S12; test pulse width)
Test pulse rate = 5 x Test pulse width
Typical response time
< 600 ms (automatic start)
< 70 ms (manual start)
Typ. starting time with U<sub>s</sub>
< 600 ms (when controlled via A1)
Typical release time
< 20 ms (when controlled via A1)
< 20 ms (when controlled via S11/S12 and S21/S22)
Delay time
K3(t), K4(t) fixed depending on model
Maximum switching frequency
Protective circuit
Surge protection; Suppressor diode
Max. permissible overall conductor resistance
approx. 11 Ω (Input and start circuits at U<sub>S</sub>)
Operating voltage display
Contact switching type
1 signaling current path
5 enabling current paths
Maximum switching voltage
250 V AC/DC (Observe the load curve)
Minimum switching voltage
Limiting continuous current
6 A (N/C contact)
6 A (N/O contact, pay attention to the derating)
Maximum inrush current
20 A (Δt 100 ms, undelayed contacts)
8 A (delayed contacts)
Sq. Total current
55 A<sup>2</sup> (observe derating)
Interrupting rating (ohmic load) max.
110 W (110 V DC, τ = 0 ms, delayed contacts: 77 W)
144 W (24 V DC, τ = 0 ms)
1500 VA (250 V AC, τ = 0 ms, delayed contacts: 2000 VA)
288 W (48 V DC, τ = 0 ms)
88 W (220 V DC, τ = 0 ms)
Maximum interrupting rating (inductive load)
42 W (110 V DC, τ = 40 ms, delayed contacts: 35 W)
42 W (220 V DC, τ = 40 ms, delayed contacts: 33 W)
42 W (24 V DC, τ = 40 ms, delayed contacts: 48 W)
42 W (48 V DC, τ = 40 ms, delayed contacts: 40 W)
Switching capacity (360/h cycles)
4 A (230 V AC)
4 A (24 V DC)
Switching capacity (3600/h cycles)
2.5 A (24 V (DC13))
3 A (230 V (AC15))
Output fuse
10 A gL/gG (N/O contact)
6 A gL/gG (N/C contact)