Rated control circuit supply voltage US
Rated control supply current IS
Application
Emergency stop
Light grid
Safety door
Mechanical service life
approx. 10<sup>7</sup> cycles
Relay type
Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Typical response time
150 ms (Monitored/manual and auto-start)
Typical release time
100 ms (delayed contacts)
20 ms (Undelayed contacts)
Delay time range
0.1 s ... 30 s ±30 % (adjustable)
Recovery time
1 s (Electric torque)
330 ms (Restart)
Maximum power dissipation for nominal condition
25.8 W (U<sub>S</sub> = 26,4 V, I<sub>L</sub>² = 120 A²)
Rated surge voltage/insulation
Rated control circuit supply voltage U<sub>S</sub>
Rated control supply current I<sub>S</sub>
Inrush current
max. 6 A
min. 25 mA
typ. 250 mA
Protective circuit
Suppressor diode
Suppressor diode, 33 V DC
Max. permissible overall conductor resistance
500 Ω (Input and reset circuit at U<sub>N</sub>)
Number of outputs
2 (delayed: 37/38, 47/48)
2 (undelayed: 13/14, 23/24)
Switching voltage
max. 250 V AC/DC
min. 15 V AC/DC
Switching capacity
3 A (24 V (DC13))
3 A (250 V (AC15))
Limiting continuous current
Sq. Total current
120 A<sup>2</sup> (observe derating)
Interrupting rating (ohmic load) max.
144 W (24 V DC, τ = 0 ms)
1500 VA (250 V AC, τ = 0 ms)
288 W (48 V DC, τ = 0 ms)
88 W (220 V DC, τ = 0 ms)
90 W (110 V DC, τ = 0 ms)
Maximum interrupting rating (inductive load)
23 W (220 V DC, τ = 40 ms)
25 W (110 V DC, τ = 40 ms)
33 W (48 V DC, τ = 40 ms)
42 W (24 V DC, τ = 40 ms)
Output fuse
10 A gL/gG NEOZED (N/O contact)
Conductor cross-section rigid
Conductor cross-section flexible
Conductor cross-section, flexible, with ferrule, with plastic sleeve
0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Conductor cross-section, flexible, with ferrule, without plastic sleeve
0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Conductor cross-section AWG
Error indication
K1/K2 and K3(t)/K4(t) LED, green