Typical input current at UN
Insulation
Basic insulation
Safe isolation, reinforced insulation, and 6 kV between input circuit and output contact current paths
Date of last data management
Maximum power dissipation for nominal condition
Test voltage (Winding/contact)
4 kV<sub>rms</sub> (50 Hz, 1 min., winding/contact)
Nominal input voltage U<sub>N</sub>
Input voltage range
179.4 V DC ... 264.5 V DC (20 °C)
Nominal voltage (plugged-in electromechanical relay)
Typical input current at U<sub>N</sub>
Protective circuit
Reverse polarity protection; Polarity protection diode
Surge protection; Freewheeling diode
Operating voltage display
Maximum switching voltage
250 V AC/DC
30 V AC
36 V DC
Minimum switching voltage
100 mV (10 mA)
5 V (at 100 mA)
Limiting continuous current
Min. switching current
1 mA (24 V)
10 mA (at 12 V)
Short-circuit current
200 A (conditional short-circuit current)
Interrupting rating (ohmic load) max.
Note
<b>the following values are applicable if a gold layer is destroyed</b>
Conductor cross-section rigid
Conductor cross-section flexible
0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1.5 mm² (TWIN ferrule)
Conductor cross-section AWG
Degree of protection (Relay base)
Ambient temperature (operation)
Ambient temperature (storage/transport)
Certificate
CE-compliant
TAE0000196
UKCA-compliant
Identification
EN 60068-2-60
ISA-S71.04. G3 Harsh Group