Order information:
Fuse-link not supplied as standard
Maximum power dissipation for nominal condition
Fuse
10.3 x 38 mm
gPV 10.3 x 38 mm in accordance with 60269-6
Number of connections per level
Internal cylindrical gage
Connection in acc. with standard
IEC 60269-1 / -2
IEC 60947-1 / -3
Conductor cross-section rigid
0.75 mm² ... 25 mm²
1 mm² ... 16 mm²
Cross section AWG
16 ... 4 (converted acc. to IEC)
18 ... 6 (converted acc. to IEC)
Conductor cross-section flexible
0.75 mm² ... 25 mm²
1 mm² ... 16 mm²
Conductor cross-section, flexible [AWG]
18 ... 4 (converted acc. to IEC)
18 ... 6 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)
0.75 mm² ... 16 mm²
1.5 mm² ... 10 mm²
Flexible conductor cross-section (ferrule with plastic sleeve)
0.75 mm² ... 16 mm²
1.5 mm² ... 10 mm²
Cross-section with insertion bridge, rigid
Cross-section with insertion bridge, flexible
2 conductors with same cross section, rigid
0.75 mm² ... 4 mm²
1 mm² ... 6 mm²
2 conductors with same cross section, flexible
0.75 mm² ... 4 mm²
1 mm² ... 6 mm²
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
0.75 mm² ... 4 mm²
1.5 mm² ... 4 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve
0.75 mm² ... 10 mm²
1.5 mm² ... 4 mm²
Nominal current
30 A (the current and voltage are determined by the fuse)
32 A (the current and voltage are determined by the fuse)
Maximum load current
30 A (the current and voltage are determined by the fuse)
32 A (the current and voltage are determined by the fuse)
Nominal voltage
1000 V DC (the current and voltage are determined by the fuse)
Flammability rating according to UL 94
Insulating material group
Ambient temperature (operation)
-60 °C ... 85 °C (max. short-term operating temperature RTI Elec.)
Ambient temperature (storage/transport)
-25 °C ... 55 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)
Ambient temperature (actuation)
Permissible humidity (operation)
Permissible humidity (storage/transport)