Order information:
Fuse-link not supplied as standard
Note
For power distribution applications, IEC 60364-4-43.2008; modified + corrigendum Okt. 2008 (DIN VDE 0100-430:2010-10) section 433.2 ff must be observed!
The current is determined by the fuse used, the voltage by the fuse or selected light indicator.
The maximum load current of a single clamping unit must not be exceeded.
Product type
Distributor terminal block
Maximum power dissipation for nominal condition
Maximum power dissipation
max. 1.6 W (With interconnected arrangement of several fuse terminal blocks in the event of overload)
max. 1.6 W (with single arrangement of the fuse terminal block in the event of overload)
max. 2.5 W (With interconnected arrangement of several fuse terminal blocks in the event of a short-circuit)
max. 4 W (with single arrangement of the fuse terminal block in the event of a short-circuit)
Number of connections per level
Stripping length
10 mm ... 12 mm
12 mm ... 14 mm
Internal cylindrical gage
Connection in acc. with standard
Conductor cross-section rigid
0.2 mm² ... 6 mm²
0.5 mm² ... 16 mm²
0.5 mm² ... 6 mm²
1.5 mm² ... 10 mm²
Cross section AWG
20 ... 6 (converted acc. to IEC)
24 ... 10 (converted acc. to IEC)
Conductor cross-section flexible
0.2 mm² ... 6 mm²
0.5 mm² ... 16 mm²
Conductor cross-section, flexible [AWG]
20 ... 6 (converted acc. to IEC)
24 ... 10 (converted acc. to IEC)
Conductor cross-section flexible (ferrule without plastic sleeve)
0.2 mm² ... 4 mm²
0.5 mm² ... 10 mm²
0.5 mm² ... 4 mm²
1.5 mm² ... 10 mm²
Flexible conductor cross-section (ferrule with plastic sleeve)
0.2 mm² ... 4 mm²
0.5 mm² ... 10 mm²
0.5 mm² ... 4 mm²
1.5 mm² ... 10 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve
0.5 mm² ... 1 mm²
0.5 mm² ... 4 mm²
Nominal current
37.8 A
6.3 A (the current is determined by the fuse used)
Maximum load current
37.8 A (with 10 mm² conductor cross-section)
6.3 A (with 4 mm² conductor cross-section)
Maximum total current
37.8 A (The maximum load current of the individual terminal point must not be exceeded.)
The maximum load current of the individual terminal point must not be exceeded.
Nominal voltage
250 V (the voltage is determined by the fuse used)
Conductor cross-section, rigid [AWG]
16 ... 8 (converted acc. to IEC)
Flammability rating according to UL 94
Insulating material group
Static insulating material application in cold
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
Relative insulation material temperature index (Elec., UL 746 B)
Fire protection for rail vehicles (DIN EN 45545-2) R22
Fire protection for rail vehicles (DIN EN 45545-2) R23
Fire protection for rail vehicles (DIN EN 45545-2) R24
Fire protection for rail vehicles (DIN EN 45545-2) R26
Calorimetric heat release NFPA 130 (ASTM E 1354)
Surface flammability NFPA 130 (ASTM E 162)
Specific optical density of smoke NFPA 130 (ASTM E 662)
Smoke gas toxicity NFPA 130 (SMP 800C)
Specification
DIN EN 50155 (VDE 0115-200):2018-05
Spectrum
Long life test category 2, bogie-mounted