Supply system configuration
Star network (TN, TT, IT (PE))
Nominal input voltage range
220 V AC ... 240 V AC
220 V DC ... 400 V DC
Input voltage range
220 V AC ... 240 V AC -15 % ... +10 %
220 V DC ... 400 V DC -15 % ... +5 %
Switch-on voltage
typ. 70 V AC
typ. 95 V DC
Shut-down voltage
typ. 50 V AC
typ. 50 V DC
Electric strength, max.
≤ 300 V AC 15 s
≤ 420 V DC
Typical national grid voltage
Voltage type of supply voltage
Inrush current integral (I2t)
Inrush current limitation
Mains buffering time
> 20 ms (185 V DC)
> 20 ms (190 V AC)
> 20 ms (230 V AC)
> 25 ms (400 V DC)
Current consumption
0.7 A (400 V DC)
1.3 A (220 V DC)
1.3 A (230 V AC)
Nominal power consumption
Protective circuit
Transient surge protection; Varistor
Input fuse
3.15 A (internal (device protection))
Recommended breaker for input protection
4 A ... 16 A (Characteristic B, C, Z)
Discharge current to PE
< 1.7 mA (264 V AC, 60 Hz)
< 3.5 mA
Power factor
> 0.9 (120 V AC)
> 0.9 (230 V AC)
Derating
< 99 V DC (2 %/V)
> 60 °C ... 70 °C (2.5 %/K)
Efficiency
typ. 92.5 % (230 V AC)
typ. 94 % (400 V DC)
Output characteristic
U/I with dynamic load reserve
Nominal output current (IN)
Dynamic Boost (IDyn.Boost)
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Control deviation
< 0.1 % (change in input voltage ±10 %)
< 1.5 % (change in load, static 10 % ... 90 %)
< 4 % (Dynamic load change 10 % ... 90 %, 10 Hz)
Residual ripple
< 20 mV<sub>PP</sub> (with nominal values)
Peak switching voltages nominal load
Maximum no-load power dissipation
typ. 4 W (230 V AC)
typ. 4 W (400 V DC)
Power loss nominal load max.
typ. 15 W (400 V DC)
typ. 20 W (230 V AC)
Rise time
20 ms (U<sub>OUT</sub> (10 % ... 90 %))
Connection in parallel
yes, for redundancy and increased capacity
Fuse protection (secondary side)
Conductor cross-section, rigid min.
Conductor cross-section, rigid max.
Conductor cross-section flexible min.
Conductor cross-section flexible max.
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.