Conductor cross-section, flexible [AWG]
CCCex note
Use in potentially explosive areas is not permitted in China.
MTTF
1014 Years (SN 29500 standard, temperature 25°C, operating cycle 21%)
178 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%)
187 Years (SN 29500 standard, temperature 40°C, operating cycle 100%)
243 Years (SN 29500 standard, temperature 25°C, operating cycle 21%)
452 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%)
MTBF
324 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day))
70 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day))
Maximum power dissipation for nominal condition
Test voltage data interface/power supply
1.5 kV<sub>rms</sub> (50 Hz, 1 min.)
Supply voltage range
18 V DC ... 30 V DC (via pluggable COMBICON screw terminal block)
Nominal supply voltage
24 V DC
24 V DC (in acc. with UL)
Typical current consumption
Max. current consumption
≤ 2 A (For operation in a joining station, via the DIN rail connector)
130 mA
Maximum switching voltage
30 V AC (Resistive load)
42 V AC (peak, resistive load)
60 V DC (Resistive Load, General Load)
Limiting continuous current
Connection method
COMBICON plug-in screw terminal block
D-SUB-9 female connector
F-SMA
Tightening torque
0.4 Nm
0.56 Nm ... 0.79 Nm
Bit delay
< 1 bit (DIP 7 = OFF, standard operation)
11 bit (DIP 7 = ON, redundancy operation)
Transmit capacity, minimum
-15.4 dBm (200/230 µm)
-3 dBm (980/1000 µm)
Transmission length incl. 3 dB system reserve
400 m (F-K 200/230 10 dB/km with quick mounting connector)
70 m (F-P 980/1000 230 dB/km with quick mounting connector)
Transmission protocol
Protocol-transparent to the RS-485 interface
Minimum receiver sensitivity
Maximum receiver sensitivity
Transmission medium
2-wire twisted pair, shielded
Copper
PCF fiber
Polymer fiber
Serial transmission speed
Transmission length
≤ 1200 m (depending on the data rate, with shielded, twisted pair data cable)
Single conductor/terminal point, rigid
Single-wire/terminal point, flexible
Max. AWG conductor cross-section, flexible
Min. AWG conductor cross-section, flexible
Single-wire/terminal point, rigid AWG max.
Single-wire/terminal point, rigid AWG min.