Maximum continuous operating voltage UC
Product type
Surge protection for information technology
Operating effective current IC at UC
Protective conductor current IPE
Nominal discharge current In (8/20) µs (line-line)
Nominal discharge current In (8/20) µs (line-ground)
Type
Attachment plug for DIN rail mounting
Pulse discharge current Iimp (10/350) µs
2.5 kA (Number of pulses category D1)
Total discharge current ITotal (8/20) µs
Voltage protection level Up (line-line)
≤ 250 V (C1 - 500 A)
≤ 250 V (C3 - 100 A)
≤ 410 V (C2 - 5 kA)
250 V (B2 - 100 A)
Voltage protection level Up (line-earth)
≤ 300 V (C3 - 100 A)
≤ 580 V (B2 - 100 A)
≤ 580 V (C1 - 500 A)
≤ 790 V (C2 - 5 kA)
Response time tA (line-line)
Conductor cross-section flexible
Response time tA (line-earth)
Conductor cross-section rigid
Conductor cross-section AWG
Color
black (RAL 9005)
silver-colored
Direction of action
Line-Line & Line-Ground/Shield
Maximum continuous operating voltage U<sub>C</sub>
Operating effective current I<sub>C</sub> at U<sub>C</sub>
Protective conductor current I<sub>PE</sub>
Nominal discharge current I<sub>n</sub> (8/20) µs (line-line)
Nominal discharge current I<sub>n</sub> (8/20) µs (line-ground)
Pulse discharge current I<sub>imp</sub> (10/350) µs
2.5 kA (Number of pulses category D1)
Total discharge current I<sub>Total</sub> (8/20) µs
Nominal pulse current Ian (10/1000) µs (line-line)
Nominal pulse current Ian (10/1000) µs (line-earth)
Nominal pulse current Ian (10/700) µs (line-line)
Nominal pulse current Ian (10/700) µs (line-earth)
Voltage protection level U<sub>p</sub> (line-line)
≤ 250 V (C1 - 500 A)
≤ 250 V (C3 - 100 A)
≤ 410 V (C2 - 5 kA)
250 V (B2 - 100 A)
Voltage protection level U<sub>p</sub> (line-earth)
≤ 300 V (C3 - 100 A)
≤ 580 V (B2 - 100 A)
≤ 580 V (C1 - 500 A)
≤ 790 V (C2 - 5 kA)
Response time t<sub>A</sub> (line-line)
Response time t<sub>A</sub> (line-earth)
Input attenuation aE, sym.
typ. 0.3 dB (≤ 2.8 MHz / 100 Ω)
typ. 3 dB (≤ 25 MHz / 100 Ω)
Cut-off frequency fg (3 dB), sym. in 100 Ω system