Electrical isolation between input and output
Signal transmission behavior
Step response (10-90%)
< 600 µs (for 4 mA ... 20 mA step)
Maximum temperature coefficient
Maximum transmission error
Transmission error, typical
< 0.05 % (of final value)
Standards/regulations
EN 61000-6-4
IEC/EN 61010-1
Rated insulation voltage
110 V DC (Power supply, input / output)
190 V AC (Power supply, input / output)
300 V<sub>rms</sub>
375 V<sub>PP</sub> (Power supply, input / output)
60 V AC/DC (Power supply, input / output)
Designation
Repeater power supply operation
Signal conditioner operation
Nominal supply voltage range
24 V AC/DC ... 230 V AC/DC -20 % ... +10 % (50/60 Hz)
Supply voltage range
19.2 V AC/DC ... 253 V AC/DC (50/60 Hz)
Max. current consumption
< 45 mA (24 V DC / 20 mA)
< 75 mA (24 V DC / 20 mA)
Power dissipation
< 1.1 W (24 V DC / 20 mA)
< 1.6 W (24 V DC / 20 mA)
Description of the input
Active current input
Passive current input
Current input signal
0 mA ... 20 mA
4 mA ... 20 mA
Transmitter supply voltage
> 15.3 V (22.5 mA)
> 16 V (20 mA)
Voltage drop
< 3.5 V (in input isolating amplifier operation)
Output description
Current output (active and passive)
Voltage output signal
0 V ... 5 V (internal resistance, 250 Ω, 0.1%)
1 V ... 5 V (internal resistance, 250 Ω, 0.1%)
Configurable via DIP switches
Current output signal
0 mA ... 20 mA (14 ... 26 V ext. source voltage)
0 mA ... 20 mA (active)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
4 mA ... 20 mA (active)
Load/output load current output
< 525 Ω (22.5 mA)
< 600 Ω (20 mA)
Output behavior in the event of an error
≥ 22.5 mA (Cable short-circuit in the input)
0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)
Conductor cross-section rigid
Conductor cross-section flexible
Conductor cross-section AWG
Status display
Green LED (supply voltage)