Electrical isolation between input and output
Signal transmission behavior
Step response (10-90%)
< 1.3 ms (for 4 mA ... 20 mA step)
Maximum temperature coefficient
Maximum transmission error
< 0.1 % (of final value 20 mA)
Transmission error, typical
< 0.05 % (of final value 20 mA)
Standards/regulations
EN 61000-6-4
IEC/EN 61010-1
Rated insulation voltage
110 V DC (Power supply, input / output)
190 V AC (Power supply, input / output)
300 V<sub>rms</sub>
375 V<sub>PP</sub> (Power supply, input / output)
60 V AC/DC (Power supply, input / output)
Test voltage
1.5 kV AC (50 Hz, 60 s)
2.5 kV AC (50 Hz, 60 s)
Max. current consumption
< 100 mA (24 V DC / 20 mA)
Power dissipation
< 1.4 W (24 V DC / 20 mA)
Transmitter supply voltage
Underload/overload signal range
Load/output load current output
≤ 375 Ω (24 mA)
≤ 450 Ω (20 mA)
Output behavior in the event of an error
< 3.6 mA (In the event of cable break at the input (as per NE 43))
> 22.5 mA (In the event of cable short circuit at the input (as per NE 43))
Conductor cross-section rigid
Conductor cross-section flexible
Conductor cross-section AWG
Status display
Green LED (supply voltage)
Depth NS 35/7,5
114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)
Flammability rating according to UL 94 (Housing)
Degree of protection
IP20 (not assessed by UL)