Input voltage range
100 V AC ... 240 V AC -15 % ... +10 %
110 V DC ... 250 V DC -20 % ... +40 %
Inrush current integral (I2t)
Frequency range (fN)
50 Hz ... 60 Hz -10 % ... +10 %
Setting range of the output voltage (USet)
5 V DC ... 6.2 V DC (constant capacity)
Typical national grid voltage
Nominal output current (IN)
Voltage type of supply voltage
Static Boost (IStat.Boost)
Dynamic Boost (IDyn.Boost)
Inrush current integral (I<sup>2</sup>t)
Inrush current limitation
POut
> P<sub>Thr</sub> (LED lights up yellow, output power > P<sub>Thr</sub>, depending on the rotary selector switch setting)
Frequency range (f<sub>N</sub>)
50 Hz ... 60 Hz -10 % ... +10 %
UOut
< 0.9 x U<sub>Set</sub> (LED flashes green)
> 0.9 x U<sub>Set</sub> (LED lights up green)
Mains buffering time
typ. 52 ms (120 V AC)
typ. 52 ms (230 V AC)
Current consumption
0.14 A (250 V DC)
0.16 A (240 V AC)
0.17 A (230 V AC)
0.3 A (120 V AC)
0.32 A (110 V DC)
0.37 A (100 V AC)
Nominal power consumption
Protective circuit
Transient surge protection; Varistor
Input fuse
3.15 A (slow-blow, internal)
Recommended breaker for input protection
6 A ... 16 A (Characteristic B, C or comparable)
Discharge current to PE
< 0.25 mA (264 V AC, 60 Hz)
typ. 0.08 mA
Efficiency
typ. 87.4 % (120 V AC)
typ. 88.4 % (230 V AC)
Setting range of the output voltage (U<sub>Set</sub>)
5 V DC ... 6.2 V DC (constant capacity)
Nominal output current (I<sub>N</sub>)
Dynamic Boost (I<sub>Dyn.Boost</sub>)
Feedback voltage resistance
≤ 16 V DC (16 V e-caps in output circuit)
Protection against overvoltage at the output (OVP)
Control deviation
< 0.1 % (change in input voltage ±10 %)
< 0.3 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10% ... 90%, 10 Hz < 4%)
Residual ripple
< 50 mV<sub>PP</sub> (with nominal values)
Maximum no-load power dissipation
< 0.37 W (120 V AC)
< 0.41 W (230 V AC)
Power loss nominal load max.
< 3.3 W (230 V AC)
< 3.7 W (120 V AC)
Crest factor
typ. 1.88 (120 V AC)
typ. 2.09 (230 V AC)
Rise time
50 ms (U<sub>Out</sub> = 10 % ... 90 %)
Connection in parallel
yes, for redundancy and increased capacity
Default
10 V DC 24 mA 10 V DC for U<sub>Out</sub> > 0.9 x U<sub>Set</sub>
Conductor cross-section, rigid min.
Conductor cross-section, rigid max.
Conductor cross-section flexible min.
Conductor cross-section flexible max.